Real, Reactive and Apparent Power
kW, kVAr, kVA and why power factor matters.
In this lesson
- Learning outcomes
- Core theory
- Trade application
- Worked example
- Workshop task
- Fault-finding notes
- Revision questions and answers
Learning outcomes
- Explain the purpose of this topic in everyday electrical work.
- Identify the circuit conditions that must be checked before relying on a reading.
- Apply the relevant calculation, test or drawing interpretation in a supervised training scenario.
- Recognise common apprentice mistakes and unsafe assumptions.
- Record evidence in a form that another tradesperson can understand.
Core theory
Alternating current is not simply DC that changes direction. The voltage and current vary sinusoidally, and the timing relationship between them matters. Resistive loads draw current in phase with voltage. Inductive loads such as motors and transformers cause current to lag. Capacitive loads cause current to lead. This phase relationship affects power factor, voltage drop and heating.
RMS values let electricians compare AC to an equivalent DC heating effect. A 230 V RMS supply has a higher peak value, but the RMS value is what is used for most power calculations. Understanding this prevents confusion when apprentices see different values on oscilloscopes, labels and calculations.
Three-phase systems are used because they deliver smoother power and efficient motor operation. The relationship between line and phase values depends on star or delta connection. A neutral conductor carries the imbalance in a star-connected system, so harmonics, load balance and borrowed neutrals must be understood before assumptions are made.
Core law
Power tells you the rate of energy conversion. Energy tells you how much is used over time. Heating is proportional to current squared through resistance, so small increases in current or connection resistance can create serious heat.
Worked example
A 230 V heater draws 8.7 A. Power is about 2.0 kW. If it runs for 3 hours it uses about 6 kWh. If a loose connection has only 0.5 Ω resistance at 8.7 A, heat at that point is I²R = 37.8 W, concentrated in a tiny area.
Textbook depth: kW, kVA and kVAr
Real power, measured in watts or kilowatts, performs useful work and produces heat, light or motion. Reactive power, measured in var or kVAr, moves energy in and out of magnetic or electric fields. Apparent power, measured in VA or kVA, is the product of RMS voltage and RMS current before power factor is applied.
Power factor is the ratio of real power to apparent power. A poor power factor means more current is required for the same real power. More current means more voltage drop and more heating in conductors and equipment. Electricians need this concept for motors, large sites, generator sizing, UPS sizing and switchboard loading.
Example: A single-phase load takes 10 A at 230 V. Apparent power is 2.3 kVA. If power factor is 0.75, real power is 1.725 kW. The conductors still carry 10 A, not the lower current implied by kW alone.
Trade application
On site, this topic is rarely isolated. It connects to safety, drawings, protection, cable selection, terminations, testing and documentation. A good apprentice does not ask only “does it work?” They ask whether it is correctly supplied, correctly protected, correctly controlled, mechanically sound, suitable for the environment, and verifiable by inspection and test.
When using this material, build a notebook of standard methods. For each topic, write the normal value, the likely fault value, the test points, the instrument setting, and the action to take if the result is abnormal. This becomes a practical diagnostic map rather than a collection of memorised definitions.
Workshop practical
Use a training transformer or simulator to compare resistive, inductive and capacitive AC loads. Record supply voltage, load current, apparent power and real power where instruments allow. Draw the phase relationship as a simple phasor diagram.
Evidence to collect: labelled sketch, predicted readings, actual readings, explanation of differences, supervisor feedback and one improvement to your method.
Fault-finding notes
- Confirm the complaint or task requirement in plain language.
- Compare the installation against the drawing, label or expected circuit arrangement.
- Prove whether supply is present at the correct point and under the correct condition.
- Divide the circuit into smaller sections instead of testing random points.
- After repair, test the protective measure, not just the load operation.
Common apprentice mistakes
| Mistake | Why it matters | Better habit |
|---|---|---|
| Measuring voltage without a reference plan | The reading may be real, induced, back-fed or meaningless without a return path. | State the exact two points being measured and the expected value first. |
| Assuming a device is faulty because it is not operating | The fault may be supply, control, protection, return path, settings or mechanical load. | Prove each section of the circuit in sequence. |
| Recording only pass/fail | Future workers cannot see whether results were strong, marginal or abnormal. | Record actual values, conditions and instrument details. |
Assessment standard
The assessor is looking for correct RMS language, recognition of phase angle, correct use of apparent/real/reactive power terms, and safe interpretation of single-phase and three-phase diagrams.
Revision questions
- What should be proven before this task is attempted on real equipment?
- Which measurement would best confirm the main idea of this lesson?
- What reading or symptom would make you stop and ask for supervision?
- How could a poor termination change the behaviour of this circuit?
- What information should be recorded for handover or assessment evidence?
Suggested answers
- Isolation, correct circuit identification, suitable supervision, correct instrument condition and an agreed safe work method.
- The measurement depends on the lesson: voltage across a component, current through a load, resistance/continuity of a path, insulation resistance between conductors, or operation time of a protective device.
- Unexpected voltage, unstable readings, signs of heat, damaged insulation, repeated protective-device operation, or any result that conflicts with the drawing.
- It can add resistance, create heat, reduce load voltage, cause intermittent operation, distort test results or prevent protective devices operating as expected.
- Circuit ID, test conditions, instrument used, actual readings, corrective actions, variations from the drawing and supervisor sign-off where required.